/probe?target=<address> once per BMC.
Endpoints
/probe takes no optional parameters. A healthy BMC publishes about 97 series: 14 fan readings, 81 temperatures, xrdu_up, and xrdu_scrape_duration_seconds.
Metrics
This is the complete supported set.
A sensor the BMC reports as not working, absent, or implausible publishes no sample. No metric marks the missing reading, so the series simply has a gap.
Labels
Join XRDU thermals with host metrics
To join BMC metrics withsambanova_* series, declare the host’s XRDU index on each target alongside node:
snctl rack show (Node/<n>/xrdu/<m>) matches the host’s index, XRDU_<m>.
Join on both node and xrdu_index. The index is not unique on its own, because XRDU_2 exists on every node.
Behavior
Data the exporter does not publish
The exporter reads the BMC’s OpenBMC sensor tree over HTTPS and maps part of it onto the metrics above. The BMC returns more in the same response. If you need any of the following, it is not available through this exporter.
To read a sensor straight from the device, bypassing the exporter:
-k and -u are required. The BMC presents a self-signed certificate and requires authentication.
Configuration
Helm values
Targets
The username defaults to
root, so you usually set only the password. Get it with snctl secret get --device-type xrdu --show-value.